A word of caution: The following article is based on National Electrical Manufacturers' Association (NEMA) tables, standards and nomenclature. This is somewhat different from Indian and European practice. The class designations are applicable only to NEMA compatible motors which are in use in the US only. However, the logic and pattern of calculations are the same everywhere. Hence the reader is cautioned to follow only the logical sequence of the calculations.
Motor Starting Current
When typical induction motors become energized, a much larger amount of current than normal operating current rushes into the motor to set up the magnetic field surrounding the motor and to overcome the lack of angular momentum of the motor and its load. As the motor increases to slip speed, the current drawn subsides to match (1) the current required at the supplied voltage to supply the load and (2) losses to windage and friction in the motor and in the load and transmission system. A motor operating at slip speed and supplying nameplate horsepower as the load should draw the current printed on the nameplate, and that current should satisfy the equation
Horsepower = (voltage X current X power factor X motor efficiency X √3) / 746
Typical induction mo
tors exhibit a starting power factor of 10 to 20 percent and a full-load running power factor of 80 to 90 percent. Smaller typical induction motors exhibit an operating full-load efficiency of approximately 92 percent, whereas large typical induction motors exhibit an operating full-load efficiency of approximately 97.5 percent.
Since many types of induction motors are made, the inrush current from an individual motor is important in designing the electrical power supply system for that motor. For this purpose, the nameplate on every motor contains a code letter indicating the kilovoltampere/horsepower starting load rating of the motor. A table of these code letters and their meanings in approximate kVA and horsepower is shown in the following table.
Code Letter on motor name plate | kVA per HP with locked rotor | ||
Minimum | Mean | Maximum | |
A | 0 | 1.57 | 3.14 |
B | 3.15 | 3.345 | 3.54 |
C | 3.55 | 3.77 | 3.99 |
D | 4 | 4.245 | 4.9 |
E | 4.5 | 4.745 | 4.99 |
F | 5 | 5.295 | 5.59 |
G | 5.6 | 5.945 | 6.29 |
H | 6.3 | 6.695 | 7.09 |
J | 7.1 | 7.545 | 7.99 |
K | 8 | 8.495 | 8.9 |
L | 9 | 9.495 | 9.9 |
M | 10 | 10.595 | 11.19 |
N | 11.2 | 11.845 | 12.49 |
P | 12.5 | 13.245 | 13.99 |
R | 14 | 14.995 | 15.99 |
S | 16 | 16.995 | 17.99 |
T | 18 | 18.995 | 19.99 |
U | 20 | 29.2 | 22.39 |
V | 22.4 | No Limit | No Limit |
Using these values, the inrush current for a specific motor can be calculated as
Iinrush=(code letter value X horse power x 1000) /( √3 X Voltage)
An example of this calculation for a 50-hp code letter G motor operating at 460 V is shown below
Because of the items listed above, motors that produce constant kVA loads make demands on the electrical power system that are extraordinary compared with the demands of constant kilowatt loads. To start them, the overcurrent protection system must permit the starting current, also called the locked-rotor current, to flow during the normal starting period, and then the motor-running overcurrent must be limited to approximately the nameplate full-load ampere rating. If the duration of the locked-rotor current is too long, the motor will overheat due to I2R heat buildup, and if the long-time ampere draw of the motor is too high, the motor also will overheat due to I2R heating. The National Electrical Code provides limitations on both inrush current and running current, as well as providing a methodology to determine motor disconnect switch ampere and horsepower ratings.
Table 430-152 of the National Electrical Code provides the maximum setting of overcurrent devices upstream of the motor branch circuit, and portions of this table are replicated below
% of Full load current | ||||
Motor type | Single element fuse | Dual-element time delay fuse | Inverse time breaker | Instantaneous & Magnetic trip breaker |
Single phase motor | 300 | 175 | 250 | 800 |
Three phase squirrel cage motor | 300 | 175 | 250 | 800 |
Design E three phase squirrel cage | 300 | 175 | 250 | 1100 |
Synchronous | 300 | 175 | 250 | 800 |
Wound rotor | 150 | 150 | 150 | 800 |
Direct current | 150 | 150 | 150 | 250 |
For example, a 50 hp, Design B, 460V 3 phase motor has a full load current of 65A at 460V. The maximum rating of an inverse time breaker protecting the motor branch circuit would be 65A x 250%, or 162.5A. The next higher standard rating is 175A (US), so 175A is the maximum rating that can be used to protect the motor circuit. |
Motor Running Current
The following figures illustrate the calculations required by specific types of motors in the design of electric circuits to permit these loads to start and to continue to protect them during operation.
Table of full-load currents for three-phase ac induction motors (A part of table 430-150 of NEC).
HP | 208 V | 230 V | 460 V | 575 V |
0.5 | 2.5 | 2.2 | 1.1 | 0.9 |
0.75 | 3.5 | 3.2 | 1.6 | 1.3 |
1 | 4.6 | 4.2 | 2.1 | 1.7 |
1.5 | 6.6 | 6 | 3 | 2.4 |
2 | 7.5 | 6.8 | 3.4 | 2.7 |
3 | 10.6 | 9.6 | 4.8 | 3.9 |
5 | 16.7 | 15.2 | 7.6 | 6.1 |
10 | 30.8 | 28 | 14 | 11 |
15 | 46.2 | 42 | 21 | 17 |
20 | 59.4 | 54 | 27 | 22 |
25 | 74.8 | 68 | 34 | 27 |
30 | 88 | 80 | 40 | 32 |
40 | 114 | 104 | 52 | 41 |
50 | 143 | 130 | 65 | 52 |
60 | 169 | 154 | 77 | 62 |
75 | 211 | 192 | 96 | 77 |
100 | 273 | 248 | 124 | 99 |
125 | 343 | 312 | 156 | 125 |
150 | 396 | 360 | 180 | 144 |
200 | 528 | 480 | 240 | 192 |
Calculating Motor Branch-Circuit Overcurrent Protection and Wire Size
Article 430-52 of the National Electrical Code specifies that the minimum motor branch-circuit size must be rated at 125 percent of the motor full-load current found in Table 430-150 for motors that operate continuously, and Section 430-32 requires that the long-time overload trip rating not be greater than 115 percent of the motor nameplate current unless the motor is marked otherwise. Note that the values of branch-circuit overcurrent trip (the long-time portion of a thermal-magnetic trip circuit breaker and the fuse melt-out curve ampacity) are changed by Table 430-22b for motors that do not operate continuously.
This is illustrated with a sample problem. Consider the circuit shown.
A 40 HP, 460 V, 3 phase, Code letter G, Service factor of 1.0 is planned for operation from a 460 V, 3 phase system. The name plate ampere is 50A. The motor is rated for continuous duty and the load is continuous. Solve for minimum sizes of branch circuit elements?
1. Take motor full load current from table 430-150 as 52A which is higher than name plate value.
2. Determine wire size: 125% of 52A = 65A.
3. Determine inverse time breaker setting: 250% of 52A = 130A, next standard rating is 150A.
4. Determine the rating of thermal overloads: 115% of 50A (name plate current) = 57.5 A
5. Determine disconnect switch ampere rating: 115% of 52A = 59.8 A
6. Determine controller HP rating: 40 HP (same as motor nameplate HP)
The completed circuit will look like this.
NEC Torque classes and characteristics
Design Letter | Starting current (%FLC) | Relative Efficiency | Slip in % rpm | Starting torque (%FLT) | Stalling torque (%FLT) |
A | Depends upon name plate code letter Normally 630-1000% | High | 3% | 120-250% | 200-275% |
B | Normally 600-700% | High | 1.5-3% | 120-250% | 200-275% |
C | Normally 600-700% | High | 1.5-3% | 200-250% | 190-225% |
D | Normally 600-700% | Medium | 5-8% | 275% | 275% |
Excerpts from EC&M's Electrical Calculations Handbook, by John M Paschal, Jr: Published by McGraw-Hill 2001.
Hello Sajith, this is a great explanation even for someone like me who has no great electrical background.
ReplyDeleteI do have a question for you. The Code Letter on motor name plate will help me find the locked rotor KVA for three phase motor. Can I use the same for single phase motor?
I am using this information to size a generator for a pump station and I understand that I need the starting KW (KVA) for sizing.
Thanks very much
Hardik
Hardik,
DeletePlease read the word of caution at the beginning of the post. The letter symbol for starting current is applicable only for NEMA motors in the U.S. IEC and Indian standards don't mention this. You can take 6-times full load current as the starting current as typical.
I like your blog on this topic is well-written and original
Deletemetering pump manufacturer in india
Hi,
ReplyDeleteIt is very informative and very helpful on my research regarding seo techniques. Thanks for sharing this post.
Induction Motor
Thank you for the article bro it is really helpful
Deletechemical dosing system
HI Sajith
ReplyDeleteCan we calculate the KVA rating of motor with HP Power of motor without using power factor ?
No, Affan, you've to know the power factor to get kVA. The steps are as below
Delete1. Get kW from HP x 0.75
2. Get full load pf from name plate, or assume 0.85 - 0.9
3. Divide kW obtained in step 1 with PF in step 2 and you get kVA (shaft)(mech)
4. Divide kVA (shaft) obtained in step 3 with motor rated efficiency from name plate or standards to get input kVA (elec)
hi sajith,
Deletenormally motor takes 6 times more current than idle current during starting, then why overload relay not tripped the motor initially??
Pratik,
DeleteMotor's overload relay is designed on the thermal principle. It will not operate on instantaneous overcurrent. Overload relay protects the motor from heating effect of sustained overload. If the starting current persists due to overload, it will definitely trip
Good Blog and thanks for your valuable information about Electric Motor. We are also Manufacturers and Supplier of Electric Motor in Tamil Nadu, India. Keep Blogging. Your Blog is very useful for us.
ReplyDeleteThis blog is absolutely useful; I love the piece of informative writing. Brakemotors
ReplyDeleteHmm I have got the vital information from here. Just love reading!
ReplyDeleteelectric motor
I hope you will share such type of impressive contents again with us so that we can utilize it and get more advantage. http://www.dealerselectric.com
ReplyDeleteVery useful blog, but I have a question.
ReplyDeleteHow come that the starting current of an induction motor will be 3-4 times larger when 3fases of 380V are connected in star than when they are in delta connection. (same load)
Very Impressive blog and awesome information shared. JMV (LPS) is the best Ac Surge Protection Devices manufacture in India. All types of surge product manufacture and Exporter in gulfs countries
ReplyDeletehow to calculate starting and running amps for 1.14HP
ReplyDeleteDC motor
Thanks for taking the time to discuss that, I feel strongly about this and so really like getting to know more on this kind of field. Do you mind updating your blog post with additional insight? It should be really useful for all of us. www.acs-advancedcooling.com
ReplyDeletei have a motor that is 40hp 460volt 3phase it has a start up 0f 220amps and running load 55 amps i have a large peak demand kw charge on electric bill how to i calculate the inrush to kw ?
ReplyDeleteHello sir, i have a query. Am dentist and i need an inverter to back up a compressor of 800W.can you please quide, which Kva would be sufficient for me. Thanks
ReplyDeleteHi one of the awesome article which I read. I have query about elevator that
ReplyDeleteWhat will be the starting current of 5hp/1hp 3ph and 1ph motor.
How can I calculate.
What's interesting to me is why the HP refers to the starting current instead of the nominal running current?? I wonder...
ReplyDeleteYour explanation was soo good... But I am still facing problem.. please give explanation for this nameplate details 2.8 kW, 0.85 p.f.,400V 3phase squirel cage I.M.
ReplyDeleteAnd also please find magnetic contactor rating
ReplyDeleteAwesome information given in detail about Motor starting and running guide.
ReplyDeleteDOL Motor Starter Manufacturers Bangalore
hello sir.. what mean if starting current and full load current is lower than it design.. is there is any effect to motors..thanks
ReplyDeleteI pay you really special thanks for sharing this informative content.
ReplyDelete3 Phase motor Cambodia
THANKS for information
ReplyDeletehello,
ReplyDeleteGood blog ! keep posting its helps us lot about
Magnetic Motor Starter
Hello Sir, If i have a 2 HP motor of 12.5 Amps load. Can i start the machine with 3 KW generator?
ReplyDeleteSo helpful and it helps the new comers in the electrical engineering field to understand.Great one and thanks
ReplyDeleteWhat is the starting current and running current of 5 hp, 3 phase ac motor ?
ReplyDeleteThis is something easier for anyone how wants to learn about electric motor current.
ReplyDelete
ReplyDeleteVery usefull informaton thanks for sharing this link share for more about AC DC Full Load Current Calculation Formula Click here
Thanks for sharing useful information. can you tell me by stopping 3 phase 11KV induction motor with average current 130 amps how much power will be save for one day.
ReplyDeleteWhat is the normal starting current of synchonous motor with 7.5 hp, 480v 3phase, 60 Hz?
ReplyDeleteWhat is the normal starting current of synchonous motor with 7.5 hp, 480v 3phase, 60 Hz?
ReplyDeleteHi , thank you for your post . we find that the no load current of an induction motor rated for 400kW , 690VAC is close to 30% of the nominal current . Will this affect the power consumption (kWH) while the motor is kept running in idle conditions we are using an inverter to run the motor,
ReplyDeleteSuch a nice blog. I liked it,as we provide Three Phase DOL Motor Starter Manufacturers for more information can visit our site.
ReplyDelete1.5 HP MOTOR . GENERATOR CAPACITY REQUIRED?
ReplyDeleteThis comment has been removed by a blog administrator.
ReplyDelete