English Electric had virtual monopoly in the electricl protective relays in India. Even now, in these times of digital architecture and computer communication with relays, you'll be surprised to find so many of these old electromechanical relays happily in service. The sensitivity and reliability of them are legendary, prompting the maintenance engineers not to part with them. The brand name has changed many times over the years, to GE, Alstom and now to Areva T&D, but the quality which lies at the base remains rock solid. Here's an application guide for the relays.
The following tables provide recommended common applications for protection of various apparatus/systems. Specific application problem not included in the tables may be referred to the manufacturer. For the sake of completeness, the following tables include some standard imported relays available with the company’s UK associates.
Table 1 - AC Generator Protection
Protection | Details | Relay Type |
Differential | 1. Unbiased, with series stabilising resistor | CAG 34 FAC 34 |
2. Biased differential | DDG 31 | |
Transverse Differential | For machine with split phase winding | CAG 34 FAC 34 |
Over current | 1. Inverse time | CDG 31 |
2. Inverse time, voltage controlled | CDV 62 | |
Stator Earth-fault | 1. Inverse time delay for generator earthed through a distribution transformer | VDG 14 |
2. For generator earthed through a resistance or solidly earthed and generator is connected to the system via delta-star transformer | CAG 14 | |
Standby Earth-fault | For generator directly connected to system | CDG 11 |
Rotor Earth-fault | Instantaneous, generally connected for alarm | VAEM 21 VME |
Field Failure | To protect against prolonged asynchronous operation. Used in conjunction with a timer and an auxiliary relay | YCGF |
Instantaneous over voltage | For over voltage protection of generator | VAGM 22 VTIG |
Time delayed over voltage | For over voltage protection of generator | VDG 11 VTU VAU |
Negative phase sequence | To detect sustained unbalance condition, relay characteristics to match machine withstand characteristic | CDN CTN |
Overload | To detect sustained overload of the machine | CTU 12 CTLM 11 |
Reverse Power | 1. Primary protection against motoring | WCD 11 |
2. Protection of diesel generators against motoring where motoring power is relatively high | CCUM WDG | |
Backup distance | To provide backup protection against uncleared system faults | YCG 15AA+VAA31 +VAT or VTT |
Forward under power interlock | Interlock against overspeed | WCD 12 |
Pole slipping | Protection against pole slipping | ZTO 11 |
Rotor temperature | To monitor rotor high temperature | DZT 4 |
Table 2 – Generator-Transformer
Protection | Details | Relay Type |
Differential | Biased, for overall phase and earth fault of the generator and generator-transformer | DTH 31/32 |
Over current | Inverse time phase and earth fault protection | CDG 31 |
Restricted earth fault | For earth fault in transformer winding | CAG 14 |
Standby earth fault | For back-up protection | CDG 11 |
Overfluxing | For protection of transformer against over excitation | GTT |
Buchholz | Protection against insipient fault in the transformer | OBGM |
Winding temperature | Protection, control and indication | TTT & CTTT |
Table 3 – Power Transformer Protection
Protection | Details | Relay Type |
Differential | Biased, for phase and earth fault protection in the transformer winding | DDT DTH |
Over current | 1. Non-directional inverse time | CDG |
2. Directional, inverse time | CDD | |
Restricted earth fault | For faults in transformer winding | CAG 14 FAC 14 |
Backup earth fault | 1. Non-directional inverse time | CDG 11 |
2. Directional, inverse time | CDD 21 | |
Buchholz | For incipient fault in the transformer | OBGM |
Time delayed earth fault | To protect the neutral earthing resistor and to provide backup protection | CDG 12 |
Temperature | Protection, control and indication | TTT & CTTT |
Voltage regulating relay and line drop compensator | For use with ON load tap changers for automatic regulation of voltage | VTJC&CIJC AVE4 & CAD |
Overfluxing | For protection against over excitation | GTT |
Table 4 – Auto Transformer
Protection | Details | Relay Type |
Differential | Unbiased, over main winding only | CAG 34 FAC 34 |
Differential | Biased, over all windings | DTH 31 DTH 32 |
Over current | Inverse time, phase and earth fault protection, non-directional or directional | CDG 31 CDD 21 |
Restricted earth fault | For earth fault in transformer winding | CAG 14 FAC 14 |
Buchholz | Protection against incipient faults in transformer | OBGM |
Winding temperature | Protection, control and indication | TTT & CTTT |
Voltage regulating relay and line drop compensator | For use with ON load tap changers for automatic regulation of voltage | VTJC&CIJC AVE4 & CAD |
Overfluxing | For protection against over excitation | GTT |
Table 5 – Unit Transformer
Protection | Details | Relay Type |
Differential | Biased, for phase and earth fault protection in the transformer winding | DDT 32 DTH 31 |
Over current | Inverse time, phase and earth fault protection without or with high set | CDG 61 CDG 31 |
Restricted earth fault | For earth fault in transformer winding | CAG 14 FAC 14 |
Neutral displacement | For detection of earth fault where low voltage system is insulated | VDG 14 |
Buchholz | Protection against incipient faults in transformer | OBGM |
Thanks for sharing these useful power tips.Keep sharing useful information like this.
ReplyDeleteMedical Hospital Furnitures
Thank you for sharing this valuable information
ReplyDeleteHi,where can I get the trip time formula for the VDG 11 relay and the time and voltage characteristic graph that include the TMS.
ReplyDeleteHi,
DeleteKeith Morris has kindly sent me the GEC Publication for VDG11 relay. You can access it through this link (https://we.tl/t-5qcTCz9I04)
Thank you Keith!
CAN you share the technical specification of English Electric make VAA11YF50A relay
ReplyDelete