1. Switchgear
The operating time of short-circuit protection shall be as short as possible and shall in any event not exceed the through-fault withstand duration of the switch board. For HV and LV 
2. Transformers
Distribution transformers shall normally be connected Dyn. The protection may consist of phase short-circuit and earth-fault by means of two-stage overcurrent relays. Stage 1 shall be IDMT and set to detect secondary side faults. Stage 2 shall be instantaneous in operation and set to detect primary side faults only. For primary voltages up to and including 6.6 kV, fused contactors may be used. 
3. Capacitors
HV capacitor banks shall comprise individually fused capacitor units. For large capacitor banks exceeding 1000 kVar, the capacitors shall be connected in double-star with unbalance protection monitoring the star-point voltages. Capacitor failure shall trip and bank and produce an alarm. Individual capacitors shall be controlled by contactors, circuit breakers, or, for LV 
4. Motors
Overload protection of electric motors that are required to remain operational in the event of fire shall be set at a minimum of 300% of the motor full load current in accordance with NFPA 20. Such motors shall be clearly identified.
5. Power and convenience outlets
Each LV 
 
 
No comments:
Post a Comment